Cable Description
- Cable Size: 2 × 16 mm²
- Standard Specification Applied to Cable: IEC 60502 - IEC 60228
- Rated Voltage: 600 / 1000 Volt
- Cable Description: Flexible Copper Conductor Insulated with XLPE and Sheathed with Polyvinyl Chloride (CU / XLPE / PVC)
Conductor
- Standard Specification Applied to Conductor: IEC 60228
- Number of Cores per Cable: 2
- Nominal Cross-Sectional Area per Core: 16 mm²
- Nominal Number of Strands per Core: 224
- Diameter of Each Strand: 0.30 mm
- Cross-Sectional Area of Each Strand: 0.07065 mm²
- Conductor Material: Copper
- Type: Class-5
- Overall Diameter of Conductor: 5.20 mm
- D.C. Resistance of Conductor at 20°C per Km (Max.): 1.21 Ω/km
Insulation
- Insulation Material: XLPE
- Core Colours: Red – Black
- Nominal Insulation Thickness per Core: 0.70 mm
- Minimum Insulation Resistance per Km at 70°C: 0.0050 MΩ·km
- Test Voltage Between Cores and Earth: 3000 V for 5 Minutes
- Heat Resistance Test: 150°C for 1 Hour
Outer Sheath
- Outer Jacket Material: PVC (Polyvinyl Chloride)
- Outer Jacket Thickness: 1.80 mm
- Outer Jacket Colour: Gray or Black
Cable Dimensions (Nominal)
- Approximate External Cable Diameter: 17.00 mm

Arabic