Cable Description
- Cable Size: 4 × 2 mm²
- Standard Specification Applied To Cable: IEC 60227 - IEC 60228
- Rated Voltage: 300 / 500 Volt
- Cable Description: Stranded Copper Conductor Insulated With Polyvinyl Chloride And Sheathed With Polyvinyl Chloride (CU / PVC / PVC)
Conductor
- Standard Specification Applied To Conductor: IEC 60228
- No. Of Cores Per Cable: 4
- Nominal Cross-Sectional Area Per Core: 2 mm²
- Nominal Number Of Strands Per Core: 7
- Diameter Of Each Strand: 0.60 mm
- Cross-Sectional Area Of Each Strand: 0.2826 mm²
- Material Of Core: Copper
- Type: Class-2
- Overall Diameter Of Conductor: 1.8 mm
- D.C. Resistance Of Conductor At 20°C Per Km (Max.): 9.14 Ω/km
Insulation
- Material Of Insulation: Polyvinyl Chloride (PVC)
- Colour Per Core: Red – Yellow – Blue – Black
- Nominal Thickness Of Insulation Per Core: 0.80 mm
- Min. Insulation Resistance Per Core Per Km Length Of Cable At 70°C: 0.0095 MΩ.Km
- Test Voltage Between Cores And Earth: 2000V for 5 min
- Heat Resistance Test: 150°C for 1 hour
Over Sheath
- Material Of Outer Jacket: Polyvinyl Chloride
- Thickness Of Outer Jacket: 1.2 mm
- Colour Of Outer Jacket: Gray Or Black
Cable Dimension (Nominal)
- Nominal External Cable Diameter: 10.1 : 12.5 mm
```

Arabic