Cable Description
- Cable Size: 3×240 + 120 mm²
- Standard Specification: IEC 60502 - IEC 60228
- Rated Voltage: 600 / 1000 Volt
- Cable Description: Stranded Copper Conductor Insulated with PVC and Sheathed with PVC (CU / PVC / PVC)
Conductor
- Number of Cores: 3 + 1
- Main Core Cross-Sectional Area: 240 mm²
- Earth/Neutral Core Cross-Sectional Area: 120 mm²
- Number of Strands (240 mm²): 61
- Number of Strands (120 mm²): 37
- Strand Diameter (240 mm²): 2.25 mm
- Strand Diameter (120 mm²): 2.02 mm
- Conductor Material: Copper
- Type: Class-2
- Cross-Sectional Area of Each Strand (240 mm²): 3.974 mm²
- Cross-Sectional Area of Each Strand (120 mm²): 3.203 mm²
- Overall Conductor Diameter (240 mm²): 20.25 mm
- Overall Conductor Diameter (120 mm²): 14.15 mm
- D.C. Resistance at 20°C (240 mm²): 0.0754 Ω/km
- D.C. Resistance at 20°C (120 mm²): 0.153 Ω/km
Insulation
- Insulation Material: PVC
- Main Core Colours: Red – Yellow – Blue
- Additional Core Colour: Black
- Nominal Insulation Thickness (240 mm²): 2.20 mm
- Nominal Insulation Thickness (120 mm²): 1.60 mm
- Minimum Insulation Resistance at 70°C: 0.0032 MΩ.km
- Voltage Test: 3000 Volt for 5 Minutes
- Heat Resistance Test: 150°C for 1 Hour
Outer Sheath
- Material: PVC
- Thickness: 2.90 mm
- Colour: Gray or Black
Dimensions
- Approx. External Cable Diameter: 61.00 mm

Arabic